中文 | EN
ASK Fixed-Frequency Hot Water Unit (Ultra-Low Temperature)

ASK Fixed-Frequency Hot Water Unit (Ultra-Low Temperature)

Categories:HEAT PUMP - Air Source Heat Pump

Introduction:Fixed-frequency air source heat pump water heater for ultra-low temperature conditions, delivering sufficient heat at -30℃ for hot water projects in cold regions.

Advantages

◆ EVI vapor injection technology delivers strong heating at ultra-low temperatures: it obtains sufficient heat even at -30℃ to meet heating demands, covering more than 95% of the populated regions in China.
◆ The unit intelligently determines whether defrosting is needed according to operating conditions, avoiding unnecessary or failed defrost cycles and reducing efficiency loss at low temperatures; combined with the anti-frost coating, frost-free running time is extended by 50% compared with the previous generation of hot water products.

ASK Fixed-Frequency Hot Water Unit (Ultra-Low Temperature) Technical Parameters
Model (HP)ASDKFXRS-18II/AASDKFXRS-36II/AASDKFXRS-54II/AASDKFXRS-90II/AASDKFXRS-180II/A
Structure TypeTop Air DischargeTop Air DischargeTop Air DischargeTop Air DischargeTop Air Discharge
Inverter / Fixed-FrequencyFixed-FrequencyFixed-FrequencyFixed-FrequencyFixed-FrequencyFixed-Frequency
System ParametersPower SupplyAC380V-3N/50HZAC380V-3N/50HZAC380V-3N/50HZAC380V-3N/50HZAC380V-3N/50HZ
Refrigerant TypeR410AR410AR410AR410AR410A
Max. Outlet Water Temperature (℃)6060606060
Dry Bulb Temperature 20℃
Wet Bulb Temperature 15℃
Initial Water Temperature 15℃
Final Water Temperature 55℃
(Hot Water Condition)
Heating Capacity (kW)18.5375295188
Power Input (kW) / Current (A)4.188.3911.7621.542.6
COP(W/W)4.424.414.424.424.41
Dry Bulb Temperature 7℃
Wet Bulb Temperature 6℃
Initial Water Temperature 9℃
Final Water Temperature 55℃
(Hot Water Condition)
Heating Capacity (kW)15.0030.0042.5085.00156.00
Power Input (kW) / Current (A)4.058.0811.5022.9042.50
COP(W/W)3.703.713.703.713.67
Dry Bulb Temperature -12℃
Wet Bulb Temperature -14℃
Initial Water Temperature 6℃
Final Water Temperature 55℃
(Hot Water Condition)
Heating Capacity (kW)10.220.53052102
Power Input (kW) / Current (A)4.348.6812.4521.5842.32
COP(W/W)2.352.362.412.412.41
Max. Power Input (kW)6.713.5193671
Max. Input Current (A)12.5253465131
Rated Flow m³/h3.206.409.0018.0032.00
Hot Water Output L/h398795112020424050
Noise dB(A)≤65≤67≤67≤69≤75

Water-Side Pressure Loss (kPa)54.0060.0075.0090.00120.00
Pipe PositionRight SideRight SideFront SideRear SideRight Side
Connection SizeG1"(Female Thread)G1-1/2"(Male Thread)G1-1/2"(Male Thread)2"(DN50)(Flange)3"(DN80)(Flange)
Unit Dimensions(mm)880×830×11621555×870×13621500×860×14302050×980×23402400×1300×2500
Net Weight(kg)1392703085951050
Note: Performance parameters of the above series are test values measured under simulated conditions and are for reference only; actual parameters shall be subject to the product nameplate. Product appearance may be updated and images are for reference only; please refer to the actual product.
  • Customer Project Cases
  • Customer Project Cases
  • Customer Project Cases